BEFORE INSTALLATION
The RP418 and RP818 Electric/Pneumatic Relays are
electrically operated pneumatic switches used for interlock
between an electrical system and a pneumatic control system.
These devices can also be used as stop and bleed valves or
as diverting or selector relays.
These relays are designed for wall mounting or panel
mounting, depending upon the application. They can be
mounted in any position without affecting the operation of the
device.
An optional 14003638-001 mounting kit is available for direct
mounting to the MP516A operators, VP519C valves or
PP901B and PP902B pressure regulators. See the Device
Mounting section.
No special tools are needed to install the RP418 and RP818
relays. Refer to job drawings for specific mounting locations.
INSTALLATION
Duct or Wall Mounting
1. Position the relay on the duct or wall and mark the
knockout mounting holes or mark the first hole and
measure 1 in. (25mm) to the second hole. See Fig. 1.
2. Drill holes for no. 8 mounting screws obtained locally.
NOTE: When wall mounting, use the mounting holes on the
sides of the relay valve body or the knockout mount-
ing holes on the inside of the splice box. See Fig. 2.
3. Attach the relay to the panel using mounting screws
obtain locally.
Panel Mounting
1. Line up the no. 8 mounting holes on the sides of the
valve body with existing holes in the panel or drill new
holes 1 in. (25 mm) apart.
2. Attach the relay to the panel using mounting screws
obtained locally.
INSTALLATION INSTRUCTIONS
NOTE: The RP418 and RP818 are functional replacements
for the RP417 and RP817. Note the difference in
location of ports 1 and 2.
2-3/4
(71)
3-3/4 (96)
RP418A,C AND RP818A
1-5/8 (42)
RP418B; RP818B
7/8 DIAMETER
KNOCKOUTS (2)
FOR 1/2 INCH
CONDUIT
GROUNDING
SCREW
1-1/4
(32)
1 (25)
5/8 (16)
KNOCKOUTS FOR
NO. 8 SCREWS
1-1/4
(32)
7/16
(15)
1-3/8
(35)
1 1 (25) 1
1 MOUNTING CENTERS FOR NO. 8 SCREWS. MOUNTING CENTERS
MAY BE UP TO 1-5/16 (35) APART TO EASE INSTALLATION.
M18376
Fig. 1. RP418 and RP818 dimensions in in. (mm).
Device Mounting
The RP418 and RP818 Relays can be mounted directly to
MP516 operators, VP519C valves, or PP901B and PP902B
pressure regulators. A mounting bracket is available in
adaptor kit 14003638-001. This bracket must be used when
mounting the relay in this manner.
1. Use the mounting holes beneath the cover of the splice
box and attach the relay using mounting screws
obtained locally. See Fig. 2 through 5.
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
95-6046EF

1 page





PáginasTotal 4 Páginas
PDF Descargar[ Datasheet RP818B.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
RP818AElectric/Pneumatic RelaysHoneywell
Honeywell
RP818BElectric/Pneumatic RelaysHoneywell
Honeywell

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar