Número de pieza | HPS3000-9 | |
Descripción | AC-DC / Distributed Power Front End 1U | |
Fabricantes | Emerson | |
Logotipo | ||
Hay una vista previa y un enlace de descarga de HPS3000-9 (archivo pdf) en la parte inferior de esta página. Total 7 Páginas | ||
No Preview Available ! Embedded Power for
Business-Critical Continuity
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
Rev. 7.10.09_81
HPS3000 Series
of 7
Special Features
• 3000 W output power
• 40 W/cu-in
• Optional customer provided air
• 1U x 3U form factor
• N+1 Redundant
• Hot-swap
• Internal OR-ing
• 5 V housekeeping
• High efficiency 89% @ 200 Vac,
100% load
• Variable speed “smart fans”
• One year warranty
Compliance
• POE Isolation
• EMI Class B - EN55022, Level “A”
• EN61000 Immunity
Electrical Specifications
Input
Input range (operating):
Input range (nominal):
Frequency:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
43 to 63 Hz
Input through Card Edge Connection
on same end as DC output
Input fusing:
Internal 25 A fuses
Both lines fused
Inrush current:
≤40 A peak
Either hot or cold start
Power factor:
0.97 typical
Meets EN61000-3-2
Harmonics:
Meets IEC 1000-3-2
requirements
@ 50% load
Input current:
19 A max input current
Holdup time:
10 ms minimum
At full rated load
Leakage current:
1.4 mA
At 240 Vac
Power line transient:
MOV directly after the fuse
Safety
• UL/cUL
• CSA
• China
• Nemko
• CB Report
• CSA 22.2
60950
60950
CCC
TUV
60950
1 page Embedded Power for
Business-Critical Continuity
Timing Signal Definitions
Turn ON/OFF Timing
Item
Description
Tvout_rise
Tsb_on_delay
48 V Output rise time
Delay from AC being applied to 5 Vsb being within regulation.
Tac_on_delay
Delay from AC being applied to all output voltages being within
regulation.
Tvout_holdup
Tpwok_holdup
Time all output voltages, including 5 Vsb, stay within regulation
after loss of AC.
Delay from loss of AC to de-assertion of PWOK
Tpson_on_delay
Tpson_pwok
Tacok_delay
Delay from PSON# active to output voltages within regulation
limits.
Delay from PSON# de-active to PWOK being de-asserted.
Delay from loss of AC input to de-assertion of ACOK#.
Tpwok_on
Tpwok_off
Tpwok_low
Delay from output voltages within regulation limits to PWOK
asserted at turn on.
Delay from PWOK de-asserted to 48 V dropping out of regulation
limits.
Duration of PWOK being in the de-asserted state during an off/on
cycle using AC or the PSON# signal.
Tsb_vout
Delay from 5 Vsb being in regulation to 48 V being in
regulation at AC turn on.
Min
5
10
5
5
10
100
1
100
50
Max
300
1500
2000
Units
msec
msec
msec
msec
msec
400 msec
50
1000
msec
msec
msec
1000 msec
msec
2000 msec
Signals and Controls - All Models
Rev. 7.10.09_81
HPS3000 Series
5 of 7
PSON #
The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal
that turns on the 48 V power rail. When this signal is not pulled low by the system, or left open, the
48 V output turns off. The 5 Vsb output remains on. This signal is pulled to a standby voltage by a
pull-up resistor internal to the power supply. The power supply fan(s) shall operate at the lowest speed.
PSON# Signal Characteristic
Signal Type
Accepts an open collector/drain input from
the system. Pulled-up to the 5 Vsb located in
power supply.
PSON# = Low
ON
PSON# = Open
OFF
MIN MAX
Logic level low (power supply ON)
0V
0.8 V
Logic level high (power supply OFF)
2.0 V
4.80 V
Source current, Vpson = low
--
4 mA
Power up delay: Tpson_on_delay
5 msec
400 msec
5 Page |
Páginas | Total 7 Páginas | |
PDF Descargar | [ Datasheet HPS3000-9.PDF ] |
Número de pieza | Descripción | Fabricantes |
HPS3000-9 | AC-DC / Distributed Power Front End 1U | Emerson |
Número de pieza | Descripción | Fabricantes |
SLA6805M | High Voltage 3 phase Motor Driver IC. |
Sanken |
SDC1742 | 12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters. |
Analog Devices |
DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares, |